GENERAL INFORMATION
|
 |
Model Type |
KING |
 |
Model Name |
KIN-525A |
 |
 |
AC INPUT
|
 |
AC Input Capacity on Battery |
525VA |
 |
AC Input Voltage |
100V or 110V/115V/120V or 220V/230V/240V, +/- 25%, Single phase |
 |
AC Input Frequency |
50 or 60 Hz+/-5% (auto sensing) |
 |
AC Input Transfer |
N/A |
 |
 |
AC OUTPUT
|
 |
AC Output Voltage |
Simulated sine wave at line input, +/-5% |
 |
AC Output Frequency |
50 or 60 Hz +/- 0.5% |
 |
AC Output Voltage Regulation |
AVR automatically increase output voltage 15% above input voltage if -9% to -25% of nominal. AVR decrease output voltage 13% below input voltage if +9% to +25% of nominal |
 |
AC Output Transfer |
2/4 milliseconds, including detection time |
 |
 |
PROTECTION
|
 |
Protection Spike |
80 Joules / 2ms |
 |
Protection Overload |
UPS automatic shutdown if overload exceeds 110% nominal at 60 sec and 130% at 3 sec |
 |
Protection Unit |
Fuse for overload & short circuit protection |
 |
Protection Short Protection |
UPS output cut off immediately or input fuse protection |
 |
 |
BATTERY
|
 |
Battery Type |
Sealed, Maintenance-free lead acid |
 |
Battery Typical |
4 hours (to 90% of full capacity) |
 |
Battery Protection |
Automatic self-test & discharge protection, replace battery indicator |
 |
 |
BACKUP TIME
|
 |
Battery Backup Time Full Load |
7 minutes |
 |
Battery Backup Time Half Load |
15 minutes |
 |
 |
PHYSICAL
|
 |
Physical Weight kgs Tower |
6.2 |
 |
Physical Weight lbs Tower |
13.7 |
 |
Physical Shipping Weight kgs |
6.5 |
 |
Physical Shipping Weight lbs |
14.3 |
 |
Physical Dimension mm Tower |
97x320x135 |
 |
Physical Dimension inch Tower |
3.8x12.6x5.3 |
 |
 |
 |
ALARM
|
 |
Alarm Battery Backup |
Slow beeping sound (about 0.47 Hz) |
 |
Alarm Battery Low |
Rapid beeping sound (about 1.82Hz) |
 |
Alarm Overload |
Continue beeping sound |
 |
 |
CONFORMANCE
|
 |
Conformance Safety |
cUL, TUV, CE, meet FCC |
 |
Conformance Surge |
Meet IEEE 587 standard |
 |
 |
ENVIRONMENT
|
 |
Environment Ambient |
3,500 meters max. elevation, 0-95% humidity non-condensing, 0-40 deg c |
 |
Environment Audible |
<40dBA (1 meter from surface) |
 |
Environment Storage Condition |
15,000 meters max. elevation |
 |
ShowOrder |