ULT-1000RM LCD
GENERAL INFORMATION
Model Type ULTIMATE LCD RM
Model Name ULT-1000RM LCD
Power Rating 1000VA
AC INPUT
AC Input Voltage 100V:76V~130V 110V:80V~138V 115V:83.5V~140V 120V:87V~140V 208V:152V~260V 220V:160V~276V 230V:167V~280V 240V:174V~280V
AC Input Frequency 50 or 60 Hz+/-3 Hz
AC Input Phase Single
AC Input Power factor >= 0.98
AC OUTPUT
AC Output Voltage 100V/110V/115V/120V or 208V/220V/230V/240V
AC Output Frequency 50Hz/60Hz (Auto detection)
AC Output Frequency Stability (+/-0.5%)
AC Output Voltage Regulation (+/-2%)
AC Output Powerfactor 0.7 (lagging)
AC Output Hamonic distortion <3% of T.H.D. at linear load
AC Output Overload detection 105% for 10 seconds and 130% +/- 10% for 300ms
AC Output Crest factor ratio ( 3:1 )
EFFICIENCY
Field49 > 85%
TRANSFER
Transfer Power failure Recovery 0 ms
Transfer Overload Disappear Auto transfer to UPS
Transfer UPS to By Pass or Vice Versa 0 ms
NOISE
Noise Level 1m Distance < 45dBA
PROTECTION
Protection Spike 125 Joules
BATTERY
Battery Type Sealed lead acid battery, free-maintenance
Battery Protection Cut off without draining any current when battery low
Battery DC Voltage 36V
BACKUP TIME
Battery Backup Time Full Load 8 minutes
Battery Backup Time Half Load 22 minutes
Battery Recharge Time About 8 hours to 90% after fully discharged
PHYSICAL
Physical Weight kgs RM 20
Physical Weight lbs RM 44.0
Physical Dimension mm RM 430x400x130
Physical Dimension inch RM 16.9x15.7x5.1
INDICATOR
LCD LCD
LCD Indicators Status Indicate line, bypass, inv, backup, fault, bat capacity, load capacity, I/P frequency, O/P voltage, O/P frequency, inside temperature, fault status
ALARM
Alarm Battery Discharge The first warning will beep every 4 seconds to indicate battery in use. The second warning will beep every 1 second to signal battery low condition
Alarm UPS Fault Continuous beeping sound
INTERFACE
Interface Dry Contact Sends AC fail and battery low signals, and receives shutdown signal from computer
Interface RS-232 Detect battery low, Schedule UPS on/off, AC input/output power status display
Interface Option Novell, SNMP, Windows NT, Window 95/98/2000/ME/XP
ENVIRONMENT
Environment Temperature 0 deg C ~ 40 deg C
Environment Humidity 0%~95% (Non condensing)