GENERAL INFORMATION
|
 |
Model Type |
ONL |
 |
Model Name |
ONL-10K31 |
 |
Power Rating |
10KVA/8KW |
 |
 |
AC INPUT
|
 |
AC Input Voltage |
220V, 285~476V |
 |
AC Input Frequency |
50 or 60 Hz+/-5 Hz |
 |
AC Input Phase |
3 Phase 3-3W, 3-4W |
 |
 |
AC OUTPUT
|
 |
AC Output Voltage |
110 / 115 / 120 / 230 / 240V |
 |
AC Output Phase |
Single |
 |
AC Output Frequency |
50Hz/60Hz |
 |
AC Output Frequency Stability |
(+/-0.5%) |
 |
AC Output Voltage Regulation |
(+/-1%) |
 |
AC Output Powerfactor |
0.8~1.0 (lagging) |
 |
AC Output Hamonic distortion |
<3% of T.H.D. at linear load |
 |
AC Output Overload detection |
125% to 150% for 20 seconds, 150% for 10 cycle |
 |
 |
EFFICIENCY
|
 |
Efficiency Whole |
> 84% |
 |
Efficiency Inverter |
> 90% |
 |
 |
TRANSFER
|
 |
Transfer Power failure Recovery |
0 ms |
 |
Transfer Overload |
Auto transfer to UPS |
 |
Transfer UPS By pass |
0 ms |
 |
 |
NOISE
|
 |
Noise Level 1m Distance |
< 60dBA |
 |
 |
BATTERY
|
 |
Battery Type |
Sealed lead acid battery, free-maintenance |
 |
Battery Protection |
Cut off without draining any current when battery low |
 |
Battery DC Voltage |
192V |
 |
 |
BACKUP TIME
|
 |
Battery Backup Time Full Load |
10 minutes |
 |
Battery Backup Time Half Load |
25 minutes |
 |
Battery Recharge Time |
About 8 hours to 90% after fully discharged |
 |
 |
PHYSICAL
|
 |
Physical Weight kgs Tower |
167 |
 |
Physical Weight lbs Tower |
367.4 |
 |
Physical Dimension mm Tower |
350x641x1010 |
 |
Physical Dimension inch Tower |
13.8X25.2X38.2 |
 |
 |
INDICATOR
|
 |
LCD Indicators Status |
Indicate line, bypass, inv, backup, fault, bat capacity, load capacity, I/P frequency, O/P voltage, O/P frequency, inside temperature, fault status |
 |
LED |
LED |
 |
 |
ALARM
|
 |
Alarm Battery Discharge |
The first warning will beep every 4 seconds to indicate battery in use. The second warning will beep every 1 second to signal battery low condition |
 |
Alarm UPS Fault |
Continuous beeping sound |
 |
 |
INTERFACE
|
 |
Interface RS-232 |
Detect battery low, Schedule UPS on/off, AC input/output power status display |
 |
Interface Option |
Novell, SNMP, Windows NT, Window 95/98/2000/ME/XP |
 |
 |
ENVIRONMENT
|
 |
Environment Temperature |
0 deg C ~ 40 deg C |
 |
Environment Humidity |
0%~95% (Non condensing) |
 |
ShowOrder |
115 |
 |
 |