GENERAL INFORMATION
|
 |
Model Type |
KING RM |
 |
Model Name |
KIN-1500APRM |
 |
 |
AC INPUT
|
 |
AC Input Capacity on Battery |
1500VA |
 |
AC Input Voltage |
(+/-) 25% at line input |
 |
AC Input Frequency |
50 or 60 Hz+/-10% (auto sensing) |
 |
 |
AC OUTPUT
|
 |
AC Output Voltage |
Simulated sine ware at 100V ro 110V/115V/120V or 220V/230V/240V +/-5% |
 |
AC Output Frequency |
50 or 60 Hz +/- 0.5% |
 |
AC Output Voltage Regulation |
AVR automatically increase output voltage 15% above input voltage if -9% to -25% of nominal. AVR decrease output voltage 13% below input voltage if +9% to +25% of nominal |
 |
AC Output Transfer |
2/4 milliseconds, including detection time |
 |
 |
PROTECTION
|
 |
Protection Spike |
320 Joules, 2ms |
 |
Protection EMI/RFI |
10dB at 0.15 MHz, 50 dB at 30 MHz |
 |
Protection Overload |
UPS automatic shutdown if overload exceeds 110% nominal at 60 sec and 130% at 3 sec |
 |
Protection Unit |
Fuse for overload & short circuit protection |
 |
Protection 10 BaseT |
Network (UTP, RJ-45) compatible jacks |
 |
Protection Short Protection |
UPS output cut off immediately or input fuse protection |
 |
 |
BATTERY
|
 |
Battery Type |
Sealed, Maintenance-free lead acid |
 |
Battery Typical |
8 hours (to 90% of full capacity) |
 |
Battery Protection |
Automatic self-test & discharge protection, replace battery indicator |
 |
 |
BACKUP TIME
|
 |
Battery Backup Time Full Load |
7 minutes |
 |
Battery Backup Time Half Load |
15 minutes |
 |
 |
PHYSICAL
|
 |
Physical Weight kgs RM |
16 |
 |
Physical Weight lbs RM |
35.2 |
 |
Physical Shipping Weight kgs |
18.5 |
 |
Physical Shipping Weight lbs |
39.6 |
 |
Physical Dimension mm RM |
483x357x84 (2U) |
 |
Physical Dimension inch RM |
19x14x3.3 |
 |
 |
 |
ALARM
|
 |
Alarm Battery Backup |
Slow beeping sound (about 0.47 Hz) |
 |
Alarm Battery Low |
Rapid beeping sound (about 1.82Hz) |
 |
Alarm Overload |
Continue beeping sound |
 |
 |
INTERFACE
|
 |
Interface RS-232 |
RS-232C Bi-directional communication port |
 |
 |
ENVIRONMENT
|
 |
Environment Ambient |
3,500 meters max. elevation, 0-95% humidity non-condensing, 0-40 deg c |
 |
Environment Audible |
<40dBA (1 meter from surface) |
 |
Environment Storage Condition |
15,000 meters max. |
 |
ShowOrder |