GENERAL INFORMATION
|
 |
Model Type |
SMART KING RM |
 |
Model Name |
SMK-2000A-RM |
 |
Power Rating |
2000 VA / 1200 W |
 |
 |
AC INPUT
|
 |
AC Input Voltage |
120V (Please call for 208V ~ 240V models) |
 |
AC Input Frequency |
50 / 60 Hz Auto Sensing |
 |
AC Input Range |
90V ~ 150V |
 |
 |
AC OUTPUT
|
 |
AC Output Waveform |
Sinewave |
 |
AC Output Voltage |
120V +/-5% of nominal, -10% of nominal after low battery warning (Please call for 208V ~ 240V models) |
 |
AC Output Frequency |
50 / 60 Hz +/- 0.5% |
 |
AC Output Voltage Regulation |
AVR automatically increase output voltage 17% above input voltage if -9% to -25% of nominal. AVR decrease output voltage 13% below input voltage if +9% to +25% of nominal |
 |
AC Output Transfer |
6 ~ 8 ms. including detection time |
 |
 |
NOISE
|
 |
Noise Level 1m Distance |
< 45 dBA |
 |
 |
PROTECTION
|
 |
Protection Spike |
320 Joules, 2ms |
 |
Protection EMI/RFI |
10dB at 0.15 MHz, 50 dB at 30 MHz |
 |
Protection Overload |
UPS automatic shutdown if overload exceeds 110% nominal at 20 sec and 125% at 5 sec |
 |
Protection Unit |
Fuse for 110V models (600VA~2500VA) and 220V models (under 1250VA), breaker for 110V model (3000VA) and 220V models (above 1500VA) |
 |
Protection Short Protection |
UPS output cut off immediately or input fuse( or breaker) protection |
 |
 |
BATTERY
|
 |
Battery Type |
Sealed, maintenance-free lead acid |
 |
Battery Protection |
Automatic self-test & discharge protection, replace battery indicator |
 |
 |
BACKUP TIME
|
 |
Battery Backup Time Full Load |
4 minutes 35 seconds |
 |
Battery Backup Time Half Load |
9 minutes |
 |
Battery Recharge Time |
4 hours to 90% |
 |
Battery Quantity |
4x 12V 7.2Ah |
 |
 |
PHYSICAL
|
 |
Physical Weight kgs |
29.9 |
 |
Physical Weight lbs |
66 |
 |
Physical Shipping Weight lbs |
72 |
 |
Physical Dimension mm Tower |
32.7 |
 |
Physical Dimension mm |
432 x 356 x 130 (W x D x H) |
 |
Physical Dimension inch |
17 x 14 x 5.1 (W x D x H) |
 |
Physical Input Inlet |
NEMA 5-15P |
 |
Physical Receptacles |
NEMA 5-15R x 4 |
 |
 |
INDICATOR
|
 |
LCD Indicators Status |
Indicate line, bypass, inv, backup, fault, bat capacity, load capacity, I/P frequency, O/P voltage, O/P frequency, inside temperature, fault status, load |
 |
LED |
LED |
 |
 |
ALARM
|
 |
Alarm Battery Backup |
Slow beeping sound (about 0.25 Hz) |
 |
Alarm Battery Low |
Rapid beeping sound (about 1.00Hz) |
 |
Alarm Overload |
Continue beeping sound |
 |
 |
INTERFACE
|
 |
Interface RS-232 |
RS-232 / USB |
 |
Interface Option |
SNMP Card |
 |
 |
ENVIRONMENT
|
 |
Environment Ambient |
2000 meters max. elevation, 0-95% humidity non-condensing |
 |
Environment Storage Condition |
15,000 meters max. elevation |
 |
ShowOrder |