SXL-1000A
GENERAL INFORMATION
Model Type SMART KING XL
Model Name SXL-1000A
AC INPUT
AC Input Capacity on Battery 1000VA
AC Input Voltage (+/-) 25% at line input
AC Input Frequency 50 or 60 Hz+/-5Hz (auto sensing)
AC Input Phase Single
AC OUTPUT
AC Output Voltage Pure sine wave at +/-5% of nominal, -10% of nominal after low battery warning
AC Output Frequency 50 or 60 Hz +/- 0.5%
AC Output Voltage Regulation AVR automatically increase output voltage 15% above input voltage if -9% to -25% of nominal. AVR decrease output voltage 15% below input voltage if +9% to +25% of nominal
PROTECTION
Protection Spike 320 Joules, 2ms
Protection EMI/RFI 10dB at 0.15 MHz, 50 dB at 30 MHz
Protection Overload UPS automatic shutdown if overload exceeds 110% nominal at 20 sec and 125% at 5 sec
Protection Unit Fuse for 110V models Except 3000A, breaker for 220V models Except 1000A
Protection Transfer Time 2/4 milliseconds (typical), including detection time
Protection Short Protection UPS output cut off immediately or input fuse( or breaker) protection
BATTERY
Battery Type Hot swappable, sealed, maintenance-free lead acid, with 3 - 6 year lifetime
Battery Typical 4 hours (to 90% of full capacity)
Battery Protection Automatic self-test & discharge protection, replace battery indicator
BACKUP TIME
Backup Time Tower Model Full Load 7 ~ 8 minutes
Backup Time Tower Model Half Load 15 ~ 18 minutes
PHYSICAL
Physical Weight kgs Tower 22.5
Physical Weight lbs Tower 49.5
Physical Dimension mm Tower 170x450x215
Physical Dimension inch Tower 6.7x17.7x8.5
INDICATOR
LED LED
MAINTENANCE
ALARM
Alarm Battery Backup Slow beeping sound (about 0.25 Hz)
Alarm Battery Low Rapid beeping sound (about 1.00Hz)
Alarm Overload Continue beeping sound
INTERFACE
Interface Dry Contact Sends AC fail and battery low signals, and receives shutdown signal from computer
Interface RS-232 Detect battery low, Schedule UPS on/off, AC input/output power status display
Interface Option Novell, SNMP, Windows NT, Window 95/98/2000/ME/XP
ENVIRONMENT
Environment Ambient 3,500 meters max. elevation, 0-95% humidity non-condensing, 0-40 deg C
Environment Audible <40dBA (1 meter from surface)
Environment Storage Condition 15,000 meters max. elevation