GENERAL INFORMATION
|
 |
Model Type |
SMART KING XL RM |
 |
Model Name |
SXL-2000ARM (3U) |
 |
 |
AC INPUT
|
 |
AC Input Capacity on Battery |
2000VA |
 |
AC Input Voltage |
(+/-) 25% at line input |
 |
AC Input Frequency |
50 or 60 Hz+/-5Hz (auto sensing) |
 |
AC Input Phase |
Single |
 |
 |
AC OUTPUT
|
 |
AC Output Voltage |
Pure sine wave at +/-5% of nominal, -10% of nominal after low battery warning |
 |
AC Output Frequency |
50 or 60 Hz +/- 0.5% |
 |
AC Output Voltage Regulation |
AVR automatically increase output voltage 15% above input voltage if -9% to -25% of nominal. AVR decrease output voltage 15% below input voltage if +9% to +25% of nominal |
 |
 |
PROTECTION
|
 |
Protection Spike |
320 Joules, 2ms |
 |
Protection EMI/RFI |
10dB at 0.15 MHz, 50 dB at 30 MHz |
 |
Protection Overload |
UPS automatic shutdown if overload exceeds 110% nominal at 20 sec and 125% at 5 sec |
 |
Protection Unit |
Fuse for 110V models Except 3000A, breaker for 220V models Except 1000A |
 |
Protection Transfer Time |
2/4 milliseconds (typical), including detection time |
 |
Protection Short Protection |
UPS output cut off immediately or input fuse( or breaker) protection |
 |
 |
BATTERY
|
 |
Battery Type |
Hot swappable, sealed, maintenance-free lead acid, with 3 - 6 year lifetime |
 |
Battery Typical |
4 hours (to 90% of full capacity) |
 |
Battery Protection |
Automatic self-test & discharge protection, replace battery indicator |
 |
 |
BACKUP TIME
|
 |
Backup Time RM Full Load |
6 ~ 7 minutes |
 |
Backup Time RM Half Load |
13 ~ 16 minutes |
 |
 |
PHYSICAL
|
 |
Physical Weight kgs RM |
26.4 |
 |
Physical Weight lbs RM |
58.1 |
 |
Physical Dimension mm RM |
483x560x130 |
 |
Physical Dimension inch RM |
19.0x22.0x5.1 |
 |
 |
 |
ALARM
|
 |
Alarm Battery Backup |
Slow beeping sound (about 0.25 Hz) |
 |
Alarm Battery Low |
Rapid beeping sound (about 1.00Hz) |
 |
Alarm Overload |
Continue beeping sound |
 |
 |
INTERFACE
|
 |
Interface Dry Contact |
Sends AC fail and battery low signals, and receives shutdown signal from computer |
 |
Interface RS-232 |
Detect battery low, Schedule UPS on/off, AC input/output power status display |
 |
Interface Option |
Novell, SNMP, Windows NT, Window 95/98/2000/ME/XP |
 |
 |
ENVIRONMENT
|
 |
Environment Ambient |
3,500 meters max. elevation, 0-95% humidity non-condensing, 0-40 deg C |
 |
Environment Audible |
<40dBA (1 meter from surface) |
 |
Environment Storage Condition |
15,000 meters max. elevation |
 |
ShowOrder |
64 |
 |
 |