GENERAL INFORMATION
|
 |
| Model Type |
ULTIMATE LED RM |
 |
| Model Name |
ULT-1000 RM LED |
 |
| Power Rating |
1KVA/700W |
 |
 |
AC INPUT
|
 |
| AC Input Voltage |
100V:76V~130V 110V:80V~138V 115V:83.5V~140V 120V:87V~140V 208V:152V~260V 220V:160V~276V 230V:167V~280V 240V:174V~280V |
 |
| AC Input Frequency |
50 or 60 Hz+/-3 Hz |
 |
| AC Input Phase |
Single |
 |
| AC Input Power factor |
>= 0.98 |
 |
 |
AC OUTPUT
|
 |
| AC Output Voltage |
100V/110V/115V/120V or 208V/220V/230V/240V |
 |
| AC Output Frequency |
50Hz/60Hz (Auto detection) |
 |
| AC Output Frequency Stability |
(+/-0.5%) |
 |
| AC Output Voltage Regulation |
(+/-2%) |
 |
| AC Output Powerfactor |
0.7 (lagging) |
 |
| AC Output Hamonic distortion |
<3% of T.H.D. at linear load |
 |
| AC Output Overload detection |
105% for 10 seconds and 130% +/- 10% for 300ms |
 |
 |
 |
TRANSFER
|
 |
| Transfer Power failure Recovery |
0 ms |
 |
| Transfer Overload Disappear |
Auto transfer to UPS |
 |
| Transfer UPS to By Pass or Vice Versa |
N/A |
 |
 |
NOISE
|
 |
| Noise Level 1m Distance |
< 45dBA |
 |
 |
PROTECTION
|
 |
| Protection Spike |
125 Joules |
 |
 |
BATTERY
|
 |
| Battery Type |
Sealed lead acid battery, free-maintenance |
 |
| Battery Protection |
Cut off without draining any current when battery low |
 |
| Battery DC Voltage |
36V |
 |
 |
BACKUP TIME
|
 |
| Battery Backup Time Full Load |
8 minutes |
 |
| Battery Backup Time Half Load |
22 minutes |
 |
| Battery Recharge Time |
About 8 hours to 90% after fully discharged |
 |
 |
PHYSICAL
|
 |
| Physical Weight lbs Tower |
N/A |
 |
| Physical Weight kgs RM |
20 |
 |
| Physical Weight lbs RM |
(44.0lb) |
 |
| Physical Dimension mm Tower |
N/A |
 |
| Physical Dimension inch Tower |
N/A |
 |
| Physical Dimension mm RM |
430x400x130 |
 |
| Physical Dimension inch RM |
(16.9 |
 |
 |
INDICATOR
|
 |
| LCD Indicators Status |
Line input (green), inverter output (green), bypass (yellow), fault (red) |
 |
| LED |
LED |
 |
 |
ALARM
|
 |
| Alarm Battery Discharge |
The first warning will beep every 4 seconds to indicate battery in use. The second warning will beep every 1 second to signal battery low condition |
 |
| Alarm UPS Fault |
Continuous beeping sound |
 |
 |
INTERFACE
|
 |
| Interface Dry Contact |
Provide power management & diagnostic functions including power status, battery low, schedule UPS ON/OFF, battery/load level display and more. Compatatible with Windows 95/98/2000/ME/NT/XP, Novell Unix and other popular systems |
 |
| Interface RS-232 |
Provide power management & diagnostic functions including power status, battery low, schedule UPS ON/OFF, battery/load level display and more. Compatatible with Windows 95/98/2000/ME/NT/XP, Novell Unix and other popular systems |
 |
| Interface Option |
N/A |
 |
 |
ENVIRONMENT
|
 |
| Environment Temperature |
0 deg C ~ 40 deg C |
 |
| Environment Humidity |
0%~95% (Non condensing) |
 |
| ShowOrder |
82 |
 |
 |