GENERAL INFORMATION
|
 |
Model Type |
KING OFFICE |
 |
Model Name |
KOF-300S |
 |
 |
AC INPUT
|
 |
AC Input Capacity on Battery |
120V: 97+/-3V~132+/-3V; 220V:180+/-6V~264+/-6V; 230V:180+/-6V~264+/-6V:240V:194+/-6V~264+/-6V |
 |
AC Input Frequency |
50 or 60 Hz+/-0.5Hz |
 |
AC Input Transfer |
2 ~ 4 milliseconds typically |
 |
 |
AC OUTPUT
|
 |
AC Output Waveform |
Simulated sine wave |
 |
AC Output Voltage |
120V or 230V +/-10% |
 |
AC Output Frequency |
50 or 60 Hz +/-5Hz (auto sensing) |
 |
 |
PROTECTION
|
 |
Protection Spike |
480 Joules, 2ms |
 |
Protection EMI/RFI |
10dB at 0.15 MHz, 50 dB at 30 MHz |
 |
Protection Overload |
UPS automatic shutdown if overload exceeds 110% nominal at 60 sec and 130% at 3 sec |
 |
 |
BATTERY
|
 |
Battery Type |
6V / 4.5Ah |
 |
Battery Typical |
4 hours |
 |
Battery Protection |
Automatic self-test & discharge protection, replace battery indicator |
 |
 |
BACKUP TIME
|
 |
Battery Backup Time Full Load |
3 minutes |
 |
Battery Backup Time Half Load |
6 minutes |
 |
 |
PHYSICAL
|
 |
Physical Weight kgs |
1.9 |
 |
Physical Weight lbs |
4.2 |
 |
Physical Shipping Weight kgs |
4.2 (9 units per carton) |
 |
Physical Shipping Weight lbs |
9.28 |
 |
Physical Dimension mm Tower |
25x9x7 |
 |
Physical Dimension inch Tower |
12x3.7x2.6 |
 |
Physical Dimension inch |
3.9x12.4x2.6 |
 |
Physical Input Inlet |
C.P.: Continental plug, E.P.: Edison Plug, A.P. Australia plug, |
 |
Physical Receptacles |
NEMA 5-15A (120V) / IEC 320 female appliance coupler (230V), 3 for surge European sockets / other countries sockets, 2 for UPS, 2 for surge |
 |
 |
 |
ALARM
|
 |
Alarm Battery Backup |
Slow beeping sound (about 0.2 Hz) |
 |
Alarm Battery Low |
Rapid beeping sound (about 1 Hz) |
 |
Alarm Overload |
N/A |
 |
 |
INTERFACE
|
 |
Interface RS-232 |
Yes |
 |
 |
ENVIRONMENT
|
 |
Environment Ambient |
3,500 meters max. elevation, 0-95% humidity non-condensing, 0-40 deg c |
 |
Environment Audible |
<40dBA (1 meter from surface) |
 |
ShowOrder |
1 |
 |
 |